Microgrid Application of Four-Leg Three-phase Inverter

( Vol-7,Issue-12,December 2020 ) OPEN ACCESS
Author(s):

José Francisco Resende da Silva, Fábio Ferreira, Hugo Miranda, Eder Mello, Marcos Rodrigues, Thobias Pereira, Rafael Nielson

Keywords:

hybrid, inverter solar, distributed, generation.

Abstract:

The On-grid inverters use energy from DC sources to feed AC consumers, and also the main grid whenever there is a surplus of energy, as distributed energy resources. A caveat of on-grid inverters generally implied by worldwide electrical standards imposes that whenever a fault occurs on the main grid, local generation must be shut off to prevent unintentional islanding. However, there are some applications where distributed resource systems could improve reliability, and on-grid inverters with off-grid function can continue to operate even when grid power outages occur, known as intentional islanding. Today’s micro-grids have better sensing capabilities and superior semiconductor technologies that allow faster response times and higher maximum ratings, improving micro-grid equipment isolation and control capabilities. In this paper, we review anti-islanding tests performed on on-grid inverters with off-grid function in Brazil for conformity assessments and present a case study of a 20 kW hybrid inverter.

Article Info:

Received: 12 Nov 2020; Received in revised form: 10 Dec 2020; Accepted: 15 Dec 2020; Available online: 25 Dec 2020

ijaers doi crossref DOI:

10.22161/ijaers.712.34